Two pipes with the same outside diameter and wall may not be equivalent in a pressure design if grade or product standard differs.
Technical considerations
Two pipes with the same outside diameter and wall may not be equivalent in a pressure design if grade or product standard differs. Allowable stress at temperature, weld factors, tolerances, corrosion allowance and connection design enter the calculation. Elbows, valves and gaskets may also limit the assembled system. A kilograms-per-metre table cannot establish a safe pressure rating. Record design pressure separately from normal operating pressure. Passing a pressure test under one set of conditions does not automatically prove suitability at another temperature or with another service fluid.
Identify the limiting system component
A thicker pipe does not raise the capacity of a lower-rated valve installed in the same line. Document the suitability of every component for the design conditions. The instantaneous gauge reading does not capture every transient or temperature change that the design may need to address. Competent responsible parties should define commissioning limits and the examination plan for the complete system.
Is test pressure the working pressure?
They are different concepts; test and operating conditions are defined by the relevant procedure and design.