Thermal expansion in stainless pipework
ÖZCAN PASLANMAZ · EST. 2002
+90 212 549 27 09[email protected]

Thermal expansion in stainless pipework

Temperature changes produce free length changes in a long stainless pipe run.

Temperature changes produce free length changes in a long stainless pipe run.

Technical considerations

Temperature changes produce free length changes in a long stainless pipe run. If movement is fully restrained, significant stresses may develop at supports and connections. An expansion calculation uses installation temperature, maximum and minimum service temperatures and the actual free length. Anchors and sliding supports must be designed as one system. Expansion joints cannot be selected by nominal diameter alone: pressure, temperature, required movement and number of cycles also matter. A single universal support-spacing figure is not a reliable design rule for every line.

Keep the intended movement path clear

Paint, a seized clamp or incorrect installation can lock a sliding support and prevent the movement assumed in the design. Distinguish anchors from sliding points during installation checks. Ensure flexible connections have room to move without striking adjacent equipment. Reviewing behaviour after the first hot operating cycle can help reveal unintended restraints before they cause recurring problems.

Does one support spacing suit every line?

No. Diameter, wall, temperature, loading and support arrangement affect the design.

Share the material, grade, dimensions and quantity so our sales team can assess your request.

Request a Quote
WhatsApp ↗